LR2-D
Model Reference

LR2-D13

LR2-D23

LR2-D33
Application
- LR2-D series of thermal relay can be used in the circuit of 50Hz or 60Hz,rated insulation voltage 660V,rated current 0.1 ~ 0.93A for protecting the phase break when the electric motor is overload.
- The relay has different mechanism and temperature compensation & can be pluged in LC1-D series AC contact. It is the most advanced thermal relay in the ninneties in the world.
Motion Characteristic: Three-phase Balance Motion Time
| No |
Times of the setting current |
Motion time |
Start condition |
Ambient temperature |
| 1 |
1.05 |
>2h |
Cold state |
20±5oC |
| 2 |
1.2 |
<2h |
Heat state(Following the No.1 test) |
| 3 |
1.5 |
<4min |
| 4 |
7.2 |
10A |
2s<Tp≤10s |
≤63A |
Cold state |
| 10 |
4s<Tp≤10s |
>63A |
Phase-losing Motion Characteristic
| No |
Times of the setting current |
Motion time |
Start condition |
Ambient temperature |
| Any two phases |
Another phase |
| 1 |
1.0 |
0.9 |
>2h |
Cold state |
20±5oC |
| 2 |
1.15 |
0 |
<2h |
Heat state(Following the No.1 test) |
Technical Data
| Type |
Number |
Setting range (A) |
Applied Contactor |
| LR2-D13 |
1301 |
0.1~0.16 |
LC1-D09~32 |
| 1302 |
0.16~0.25 |
LC1-D09~32 |
| 1303 |
0.25~0.4 |
LC1-D09~32 |
| 1304 |
0.4~0.63 |
LC1-D09~32 |
| 1305 |
0.63~1 |
LC1-D09~32 |
| 1306 |
1~1.6 |
LC1-D09~32 |
| 1307 |
1.6~2.5 |
LC1-D09~32 |
| 1308 |
2.5~4 |
LC1-D09~32 |
| 1310 |
4~6 |
LC1-D09~32 |
| 1312 |
5.5~8 |
LC1-D09~32 |
| 1314 |
7~10 |
LC1-D09~32 |
| 1316 |
9~13 |
LC1-D09~32 |
| 1321 |
12~18 |
LC1-D09~32 |
| 1322 |
17~25 |
LC1-D32 |
| LR2-D23 |
2353 |
23~32 |
LC1-D09~32 |
| 2355 |
30~40 |
LC1-D09~32 |
| LR2-D33 |
3322 |
17~25 |
LC1-D09~32 |
| 3353 |
23~32 |
LC1-D09~32 |
| 3355 |
30~40 |
LC1-D09~32 |
| 3357 |
37~50 |
LC1-D09~32 |
| 3359 |
48~65 |
LC1-D09~32 |
| 3361 |
55~70 |
LC1-D09~32 |
| 3363 |
63~80 |
LC1-D09~32 |
| 3365 |
80~93 |
LC1-D95 |
| LR2-D43 |
4365 |
80~104 |
LC1-D95 |
| 4367 |
95~120 |
LC1-D95~115 |
| 4369 |
110~140 |
LC1-D115 |
| 5360 |
90~150 |
LC1-D150 |
Dimensioned