Split Core Current Transformer
UK
Application
- For installation into existing networks without disconnecting cable circuits. The fast action clip function ensures a high speed permanent installation.
Description
- Split-core transformer, with a unique clip-togetherfeature. Supplied in a moulded case with 1 metreflying leads. Suitable for primary ranges up to800A with 5A secondary.
- IEC60044-1, EN60044-1, VDE0414-44-1, GB1208-2006
Specifications
| Rated Frequency | 50/60Hz |
| Rated Test Voltage | 3KV AC (1min) |
| Rated shot-time thermal current (Ith) | 60In |
| Rated dynamic current (Idyn) | 2.5Ith |
| Rated voltage (Um) | 0.72KV AC |
| Continuous overload (Id) | 1.2In |
| Operating temperature | -10°C ~ 50°C |
| Housing self-extingusishing class | VO |
| Safety factor | FS 5 |
| Secondary current | 5A, 1A |
Technical Data
UK-40| Type | Ration (A) | Burden (VA) | |
| Class: 0.5 | Class:1.0 | ||
| UK-40 | 100/5 | 1.5 | 2.5 |
| 150/5 | 1.5 | 2.5 | |
| 200/5 | 2.5 | 2.5 | |
| 250/5 | 2.5 | 2.5 | |
| 300/5 | 2.5 | 5 | |
| 400/5 | 5 | 5 | |
| 500/5 | 5 | 5 | |
| 600/5 | 5 | 5 | |
| 800/5 | 5 | 5 | |
Dimensioned
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |